"Pressure differential is outside of set limits" alarm will not go away  

  RSS

Operator
Active Member
Joined: 5 months  ago
Posts: 17
10/05/2017 6:53 pm  

What do I do?


ReplyQuote
dstaheli
New Member
Joined: 5 months  ago
Posts: 1
10/05/2017 9:01 pm  

Most likely cause is that one or both of the steam pressure sensors has gone bad and needs to be replaced. 

Other causes could be:

  • pig tail drain valve left open on one of the sensors
  • Input card channel for one of the steam pressure sensors is fried.

ReplyQuote
Brian
Eminent Member
Joined: 5 months  ago
Posts: 21
11/05/2017 4:07 pm  

Use the "Pressure Differential Alarm" section in the 6110 Troubleshooting Guide or 6210 Troubleshooting Guide found in the Customer Portal

 

See attachment: